ABB Mini Contactor
这个型号是德国产,有15个现货,微型宽脚接触器,如需购买,请发邮件。
B7-30-10-F
General Information
- Extended Product Type:
- B7-30-10-F-01
- Product ID:
- GJL1311003R0101
- EAN:
- 4013614157417
- Catalog Description:
- B7-30-10-F-01 Mini Contactor 24V 40-450Hz
- Long Description:
- The B7-30-10-F mini contactor is a compact 3 pole contactor with 1 auxiliary contact and flat pin connection. They are ideally suited for applications where reliability is a must and space is at a premium. Mini contactors are used in residential buldings, commercial buildings and industrial applications for the control of single or three-phase loads up to 5.5 kW (AC-3) and 20 A / 690 V (AC-1) or switching of control signals. Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Mini Contactors
Accessories
Ordering
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85365080
Popular Downloads
- Data Sheet, Technical Information:
- 1SBC100173C0201
- Dimension Diagram:
- GJL1200437F0001
Dimensions
- Product Net Width:
- 52.5 mm
- Product Net Height:
- 57.5 mm
- Product Net Depth:
- 46.5 mm
- Product Net Weight:
- 0.17 kg
Technical
- Number of Poles:
- 4
- Mini Contactor Type:
- Mini Contactor
- Rated Operational Voltage:
- Auxiliary Circuit 12 ... 240 V DC
Auxiliary Circuit 12 ... 500 V AC/DC
Main Circuit 12 ... 690 V AC/DC
Main Circuit 690 V AC
- Rated Frequency (f):
- Control Circuit 400 Hz
Control Circuit 50 Hz
Control Circuit 60 Hz
Main Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit DC
- Rated Impulse Withstand Voltage (Uimp):
- Auxiliary Circuit 6 kV
Main Circuit 6 kV
- Rated Insulation Voltage (Ui):
- 690 V
acc. to UL/CSA 600 V
- Number of Main Contacts NC:
- 0
- Number of Main Contacts NO:
- 3
- Rated Operational Current AC-1 (Ie):
- (220 / 240 V) 40 °C 20 A
(220 / 240 V) 55 °C 16 A
(380 / 440 V) 40 °C 20 A
(380 / 440 V) 55 °C 16 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
- Rated Operational Power AC-3 (Pe):
- (220 / 230 / 240 V) 3 kW
(400 V) 5.5 kW
(400 V) Three Phase 5.5 kW
(440 V) 5.5 kW
(500 V) 5.5 kW
(690 V) 3 kW
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
- Number of Auxiliary Contacts NC:
- 0
- Number of Auxiliary Contacts NO:
- 1
- Rated Operational Current AC-15 (Ie):
- (120 V) 4 A
(220 / 240 V) 4 A
(24 V) 4 A
(380 / 400 V) 3 A
(500 V) 2 A
- Rated Operational Current DC-13 (Ie):
- (110 V) 0.7 A
(220 / 240 V) 0.4 A
(24 V) 2.5 A
- Conventional Free-air Thermal Current (Ith):
- Main Circuit 20 A
- Rated Control Circuit Voltage (Uc):
- 24 V AC
- Coil Operating Limits:
- (acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
- Degree of Protection:
- Auxiliary Circuit Terminals IP20
Control Circuit Terminals IP20
Main Circuit Terminals IP20
- Mechanical Durability:
- 10000000 cycle
- Minimum Switching Capacity:
- 17 V
5 mA
- Maximum Electrical Switching Frequency:
- AC-1 300 cycles per hour
AC-15 600 cycles per hour
AC-3 600 cycles per hour
DC-1 600 cycles per hour
DC-13 600 cycles per hour
DC-3 600 cycles per hour
- Mounting on DIN Rail:
- TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- Power Loss:
- at Rated Operating Conditions per Pole 2 W
- Standards:
- IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1